Testing & maintenance

Emergency Lighting Testing Intervals: Monthly, Annual, 5-Yearly

8 min readLast updated: October 2026NOTLUX editorial team · TRiALED GmbH
In short

Under EN 50172:2024, emergency lighting is given a short function test every month and a full rated-duration test once a year; every 5 years the illuminance is also measured. Depending on the testing basis defined for the system, central battery systems may additionally require a daily reading of their indicators, and older requirements may still apply to existing installations. On top of this, national rules require periodic electrical inspections and, for certain high-risk buildings, inspections by approved experts; every test is recorded in the logbook.

Which testing intervals apply to emergency lighting?

A testing interval is the maximum period after which a specific test of the emergency lighting must be repeated. Across Europe, the baseline is EN 50172:2024 (emergency escape lighting systems); in Germany it is published as DIN EN 50172 (VDE 0108-100):2024-10. National documents and rules add to it, for example BS 5266-1 in the UK, together with occupational safety law and building regulations.

IntervalTestWhat is checkedTypically carried out by
Daily (depending on the defined testing basis)Reading the indicatorsOperating and fault indications on central or group battery systemsInstructed staff of the operator
MonthlyFunction testSwitch to emergency mode, every luminaire and exit sign lights up, then return to normal mode and indicators workingInstructed person (via test button/test function) or qualified electrician, depending on system
AnnuallyFull rated-duration testSystem operates for the full required time (e.g. 1 h or 3 h); condition and soiling of luminaires, rest/inhibit functions where presentQualified electrician
Every 5 yearsIlluminance measurementIlluminance in emergency mode under EN 50172:2024, section 7.4.5; measurement report kept with the logbookQualified electrician or specialist contractor with a meter
Periodically (national rules)Electrical installation inspectionProtective measures, insulation, connections, condition of componentsQualified electrician
High-risk buildings, e.g. often every 3 years in GermanyInspection by approved expertsEffectiveness and reliability under building lawOfficially recognised inspection experts
OngoingCondition checkDamaged or obscured luminaires and signs, escape routes changed by refurbishmentOperator

Which intervals are binding for a given building depends on its use, the building permit, the fire safety strategy and national law. For an overview of the standards, see emergency lighting standards.

Which testing basis applies to your system?

Example Germany: DIN EN 50172 (VDE 0108-100):2024-10 replaces the 2005-01 edition and the former German pre-standard DIN VDE V 0108-100-1:2018-12, with a transition period until 27 May 2027. For existing installations, older test requirements may still apply on a building-specific basis – for example weekly function checks under the former pre-standard, where the building permit, an inspection report or the fire safety strategy refers to them.

As the operator, you should therefore define which testing basis and which intervals apply to your system and record this in the logbook. If in doubt, clarify it with your electrical contractor, the inspection expert or the building authority.

Daily reading of indicators: central power supply systems

A daily reading of the indicators concerns systems with a central power supply, meaning central or group battery systems, and is required depending on the defined testing basis. Someone reads the control panel to confirm that the system is ready and shows no fault. Self-contained luminaires have no central unit whose indicators would need reading every day. The differences are explained in self-contained vs central battery.

Monthly function test: short but complete

In a function test, every luminaire is switched to emergency mode, usually via a test button, a test function or the central unit. The test lasts only as long as needed to confirm that all luminaires and exit signs are lit – it should not significantly discharge the batteries. Afterwards, check that the luminaires return correctly to normal mode and that status and fault indicators work. Failed luminaires are recorded as defects and repaired promptly.

Annual duration test: the full rated time

In a duration test, the system must run in emergency mode for its full rated duration, for example one or three hours. Only this test shows whether the system will do its job in a real emergency. The annual test also covers the condition and soiling of the luminaires and, where present, rest and inhibit functions. Which duration a building needs is covered in emergency lighting duration.

How should the duration test be planned?

After a full discharge the batteries are empty and must recharge, which can take up to 24 hours. Sufficient safety lighting must still be available during the test and the recharging period. The usual approach is therefore to run the duration test outside hours of use, or to define substitute measures for that time.

Splitting the luminaires into two groups does not in itself guarantee this: you still need to check that every escape route is adequately lit by the remaining group and whether the building is in use during recharging.

What if a luminaire does not reach its rated duration?

A luminaire that fails to reach the required duration has a defect – not something to note down for later. It is recorded in the logbook and must be remedied promptly and properly; in Germany, ASR A2.3, section 9 (10), requires defects to be eliminated without delay. Temporary measures must be defined until then. The cause is not always the battery; electronics, light source or charging circuit may also be involved.

Practical tip: Plan the duration test with your electrician so that it takes place outside hours of use and leaves enough time for recharging before the building is used again. Record both the rated duration and the duration actually tested in the logbook.

Worked example: how much testing per year?

Assume an office building with 80 self-contained luminaires (60 escape route luminaires, 20 exit sign luminaires) and a rated duration of 3 hours.

  • Monthly function tests: 80 luminaires × 12 months = 960 individual tests per year.
  • Annual duration test: 80 individual tests, giving 1,040 test operations a year that must be carried out and recorded.
  • Timing the duration test: for example on a Friday evening, so that the batteries recharge over the weekend before the building is used again on Monday.
  • Time required: assuming 2 minutes per luminaire for triggering, checking and recording, the function tests alone add up to around 32 working hours a year – excluding walking time, ladders and access platforms.
  • Every 5 years in addition: the illuminance measurement with a measurement report.

The example shows why testing often slips in day-to-day operation, and why automatic test systems are economically attractive.

Periodic inspections and expert inspections

Beyond the operator's routine tests, further duties apply:

  • Electrical inspection: emergency lighting is part of the electrical installation and is inspected periodically by a qualified electrician. In Germany, for example, this follows from the Ordinance on Industrial Safety and Health (BetrSichV) and DGUV Regulation 3, with the interval set by the employer's risk assessment.
  • Approved experts: in Germany, the state inspection ordinances (Prüfverordnungen) generally require high-risk buildings such as assembly venues, large retail premises, high-rise buildings or large car parks to be inspected before first use, after major changes and then periodically, often every three years. Other countries have comparable but different schemes.
  • Fire safety inspections: authorities may review both the installation and the logbook.

More on this in authority inspections. Who may carry out which test is explained in who may test emergency lighting.

How do self-testing luminaires change the intervals?

The intervals stay the same – what changes is who triggers the test. Automatic test systems to EN 62034 carry out the monthly function test and the annual duration test themselves, store the results and report faults via a status LED, a central panel or an app.

What remains: the visual check for damage and obscured signs, checking condition and soiling, the 5-yearly measurement, reviewing the records, repairing defects and keeping the logbook. NOTLUX Series 19 luminaires, for example, self-test in line with EN 50172 and EN 62034 and provide the results via Bluetooth in an app. Read more in self-testing emergency lights.

Checklist: staying on top of testing intervals

  • Define the applicable testing basis and intervals and record them in the logbook.
  • Name the responsible person in writing, including a deputy.
  • Keep a luminaire layout plan with a unique number for every luminaire and sign.
  • Put function and duration tests in the calendar as fixed dates.
  • Plan duration tests outside hours of use or with substitute measures, including recharging time.
  • Track the due dates for the 5-yearly measurement and for electrical and expert inspections.
  • Record defects with the measure taken, the date fixed and the retest result.

Hand over the deadlines: With the NOTLUX maintenance contract we take care of the annual on-site inspection, the digital logbook and monitoring of all deadlines. From 2027, remote maintenance is added.

Read more: EN 50172:2024 – what has changed?.

Never miss a test date againMonthly function test and annual duration test as a calendar file – with reminders, for Outlook, Google and Apple.Create test calendar
NOTLUX Wartung · logbook app

Tired of paperwork?

Print, fill in, file, type up – or simply use the app: tap the luminaire on the plan, record defects with a photo, get the report at a click. For existing emergency lighting of any make.

  • Import your existing Excel list – no fresh start
  • Report ready right after the walk-through, no typing up later
  • All sites, luminaires and defects at a glance
  • Servers in Frankfurt, GDPR-compliant, works offline
2 minutes · no sign-up · sample building
NOTLUX Wartung – testing luminaires on the plan
Emergency lighting test report template
PDF · 4 pages · 460 KB

Emergency lighting test report template

4 pages for commissioning, the annual test and testing after modification: reason and testing basis, 12 test items, duration test with rated and achieved duration, illuminance, results per luminaire, rated defects, result and signatures.

Download PDF Printer-friendly version (saves toner) · 461 KB Also as an Excel template to fill in on your computer · 15 KB

Frequently asked questions

How often should emergency lights be tested?

Under EN 50172:2024, monthly as a function test, annually for the full rated duration and every 5 years with an illuminance measurement. Depending on the defined testing basis, further checks may apply, such as a daily reading of indicators on central battery systems. National rules add electrical inspections and, for certain buildings, expert inspections.

Do weekly checks under DIN VDE V 0108-100-1 still apply in Germany?

The pre-standard DIN VDE V 0108-100-1:2018-12 has been replaced by DIN EN 50172 (VDE 0108-100):2024-10, with a transition period until 27 May 2027. For existing installations, weekly checks may still be required on a building-specific basis. What counts is the testing basis defined for the system, which should be recorded in the logbook.

How long does the monthly function test take?

Only as long as it takes to confirm that every luminaire and exit sign works in emergency mode and then returns correctly to normal mode. The test should not significantly discharge the batteries. Most of the effort comes from walking the building and recording the results.

Why should the duration test not be done during occupied hours?

After the test the batteries are discharged and may need up to 24 hours to recharge. Sufficient safety lighting must remain available during the test and the recharging period. That is why tests are run outside hours of use or with substitute measures; splitting into two groups alone is not enough.

What if a luminaire fails the duration test?

That is a defect. It must be recorded and remedied promptly and properly, with temporary measures defined in the meantime. The cause may lie beyond the battery.

Do self-testing luminaires remove the need for testing?

No. Automatic test systems to EN 62034 take over the function and duration tests, but the intervals still apply. Visual checks, the 5-yearly measurement, reviewing the records, repairing defects and documentation remain the operator's responsibility.

NOTLUX Symbol
NOTLUX editorial team · TRiALED GmbHSpecialist editors for emergency and safety lighting
NOTLUX

Emergency lighting without worries.

Luminaires, installation and maintenance from a single source – every inspection documented digitally in our app. We start with a free on-site survey and standard-compliant design.

Get a quotein 30 seconds