Emergency Lighting Standards: EN 1838, EN 50172 and More

9 min readLast updated: October 2026NOTLUX editorial team · TRiALED GmbH
In short

The core European standards for emergency lighting are EN 1838 (lighting requirements), EN 50172:2024 (design, installation, operation and testing of systems), EN 60598-2-22 (emergency luminaires as products), EN 62034 (automatic test systems), EN 50171 (central power supply systems) and ISO 7010 (safety signs). Whether a building needs emergency lighting at all is decided by national law, such as workplace and building regulations; many countries also have national rules alongside the EN standards. In Germany, DIN EN 50172 (VDE 0108-100):2024-10 replaces both the 2005 edition and the former pre-standard DIN VDE V 0108-100-1, with a transition period until 27 May 2027.

How do laws, regulations and standards fit together?

No single rule covers emergency lighting from start to finish. The rules form a hierarchy with different levels of legal force:

  • Laws and regulations decide whether safety lighting is required. In the EU, the Workplace Directive 89/654/EEC sets the minimum for workplaces; national building codes add requirements for buildings with special use or high occupancy. These are directly binding.
  • Official technical rules specify the regulations in more detail. In Germany, for example, the technical rules for workplaces (ASR) give a presumption of conformity with the Workplace Ordinance.
  • Standards describe how an installation is designed, built and tested. On their own they are voluntary, but they represent the generally recognised state of the art and become binding in practice through permits, contracts and references in regulations.

In practice: whether your building needs emergency lighting follows from the risk assessment or building permit. How it is designed, installed and tested follows from the standards. See when emergency lighting is required.

Which standards and rules apply?

The first part of the table lists the European and international standards that form the common basis across Europe. The second part shows German rules as an example of national requirements.

Standard or ruleWhat it covers
EN 1838Lighting requirements: illuminance, uniformity, response times, minimum duration, visibility of safety signs
EN 50172:2024Emergency lighting systems: design, installation, operation, periodic testing, handover documentation and logbook
ISO 30061 (CIE S 020)International standard for emergency lighting with lighting requirements; in Europe the related EN 1838 applies
EN 60598-2-22Product standard for emergency luminaires: safety, construction, marking, battery operation
EN 62034Automatic test systems for battery-powered emergency escape lighting
EN 50171Central safety power supply systems (central and group battery systems)
ISO 7010 (EN ISO 7010)Registered safety signs, including green exit and escape route signs
Directive 92/58/EECEU minimum requirements for safety signs at work
Germany: DIN EN 50172 (VDE 0108-100):2024-10German edition of EN 50172:2024; replaces DIN EN 50172:2005-01 and the former pre-standard DIN VDE V 0108-100-1:2018-12 (transition until 27 May 2027)
Germany: DIN VDE 0100-560Low-voltage installations: equipment for safety services, including safety power circuits
Germany: DIN VDE 0100-718Low-voltage installations in public facilities and workplaces
Germany: DIN VDE 0100-710Low-voltage installations in medical locations, including safety power supply
Germany: ASR A1.3Safety and health signage at work, including exit signs
Germany: ASR A2.3Escape routes and emergency exits in workplaces, signage and safety lighting
Germany: ASR A2.3, ASR A3.4, ASR A1.3 (formerly also ASR A3.4/7)German workplace rules: safety lighting and optical guidance systems now mainly in ASR A2.3 (section 9), general lighting in ASR A3.4, signs in ASR A1.3
Germany: MLARModel guideline on cable installations: fire protection of wiring, including circuit integrity for safety lighting
Germany: MBO / state building codesWhether safety lighting is required under building law, for example in places of assembly, shops, hotels, high-rise buildings and car parks

In German usage the European standards carry a "DIN" prefix, for example DIN EN 1838 or DIN EN 50172; the content is the same. Standards are revised periodically. The current edition is generally decisive, although for existing installations the edition in force at the time of installation, or a testing basis defined for the specific building, can be relevant.

EN 1838: how bright must emergency lighting be?

EN 1838 is the lighting standard for emergency lighting. It sets the illuminance required on escape routes, in open (anti-panic) areas, at high-risk task areas and at safety equipment. Typical values are at least 1 lx on the centre line of escape routes, 0.5 lx for anti-panic lighting and 5 lx vertical at fire extinguishers, call points and first aid points. All values, uniformity ratios and response times are explained in emergency lighting illuminance.

EN 50172:2024: how are systems designed and tested?

EN 50172:2024 is the current European system standard for emergency lighting installations. It covers design, installation, operation, the periodic tests, handover documentation and the logbook. Several countries have national rules alongside it. Example Germany: the standard is published as DIN EN 50172 (VDE 0108-100):2024-10 and replaces both the 2005-01 edition and the national pre-standard DIN VDE V 0108-100-1:2018-12, which was previously applied in addition. Example United Kingdom: BS 5266-1 provides the national code of practice.

For operators, the test intervals matter most: a monthly function test, an annual full-duration test and, new in the 2024 edition, an illuminance measurement every 5 years. Depending on the testing basis defined for the system, central battery systems may also require a daily reading of the indicators. Details are in testing intervals.

What changed with the 2024 edition?

The new edition explicitly changed the requirements for tests, handover documentation and the logbook. The key points for operators:

  • Illuminance measurement every 5 years: under section 7.4.5, the illuminance is measured every 5 years, and the measurement report is kept with the logbook.
  • Documentation: handover documents and the logbook are more clearly specified. What a complete logbook contains is explained in emergency lighting logbook.
  • Example Germany – one standard instead of two: the pre-standard DIN VDE V 0108-100-1 has been replaced. The previous documents may still be applied until 27 May 2027.

For existing installations, older test requirements may still apply on a building-specific basis – in Germany, for example, weekly function checks under the former pre-standard, where the building permit, an inspection report or the fire safety strategy refers to them. Operators should therefore define the testing basis and intervals that apply to their system and record them in the logbook.

EN 60598-2-22 and EN 62034: what applies to the luminaire itself?

EN 60598-2-22 is the product standard for emergency luminaires. It covers electrical safety, construction, marking and behaviour in battery mode. Any emergency luminaire you buy should be verifiably tested to this standard.

EN 62034 describes automatic test systems: the luminaire or a central controller carries out function and duration tests on its own and stores the result. The NOTLUX Series 19 luminaires work on this principle, with a monthly function test, an annual duration test and log export via an app. How this works in practice is explained in self-testing emergency lights.

Practical tip: An automatic test system replaces the electrical tests, not the visual inspection. Damaged luminaires, obstructed exit signs or escape routes changed by refurbishment still need to be spotted by a person.

EN 50171 and wiring rules: what applies to central battery systems?

Systems with a central power supply bring further rules into play. EN 50171 sets the requirements for central safety power supply systems, meaning the battery system itself. National wiring rules govern the safety circuits. Example Germany: DIN VDE 0100-560 covers the installation of safety circuits, and the MLAR requires that cables supplying safety lighting remain functional for a defined time in a fire (circuit integrity), which calls for special cables, support systems or shafts.

With self-contained luminaires, the battery sits inside the luminaire. Circuit integrity for the supply cables is then generally not required, because each luminaire switches to its own battery when its mains supply fails. See self-contained vs central battery.

ISO 7010: what applies to exit signs?

ISO 7010 contains the internationally registered safety signs. For escape routes, the signs E001 and E002 (emergency exit, left and right hand) and the supplementary direction arrows are the most relevant. The EU Safety Signs Directive 92/58/EEC sets the minimum requirements for signage at work, and countries transpose it nationally; in Germany this is done through ASR A1.3. Germany's former ASR A3.4/7 on safety lighting was withdrawn in 2022 and split across ASR A2.3, ASR A3.4 and ASR A1.3, but many older documents and fire safety strategies still cite it; see ASR A2.3 and A3.4: safety lighting in German workplaces.

How do national rules differ across Europe?

The EN standards and ISO 7010 provide a common technical basis throughout Europe. When emergency lighting is required, which rated duration applies and who inspects it are decided nationally, and many countries have supplementary standards. An overview is given in emergency lighting in Europe.

The lighting requirements in detail: EN 1838 explained.

Read more: EN 50172:2024 – what has changed?.

Frequently asked questions

Which is the most important emergency lighting standard?

There is no single standard. EN 1838 covers the lighting requirements, EN 50172 the installation from design to testing. For operators, the testing and documentation requirements of EN 50172:2024, plus any national rules, are usually the most relevant.

Are emergency lighting standards legally binding?

Standards are not laws. However, they represent the recognised state of the art and become binding through permits, contracts and references in regulations. If you deviate from them, you may have to prove that an equivalent level of safety is achieved.

Is the German DIN VDE V 0108-100-1 still valid?

The pre-standard DIN VDE V 0108-100-1:2018-12 has been replaced, together with DIN EN 50172:2005-01, by DIN EN 50172 (VDE 0108-100):2024-10. The transition period runs until 27 May 2027. For existing installations, older test requirements may still apply on a building-specific basis; the testing basis should be recorded in the logbook.

Is the old German DIN VDE 0108 still valid?

No. DIN VDE 0108 has been withdrawn; its content is now mainly found in EN 1838, EN 50172 (VDE 0108-100), EN 50171, DIN VDE 0100-560 and DIN VDE 0100-718. Systems built to it can usually remain in service. See DIN VDE 0108.

What is new in EN 50172:2024?

The 2024 edition mainly changed the requirements for tests, handover documentation and the logbook. One addition is an illuminance measurement every 5 years under section 7.4.5, with the measurement report kept with the logbook.

Which standard applies to self-testing emergency lights?

Automatic test systems for battery-powered emergency escape lighting are described in EN 62034. The luminaire must also meet the product standard EN 60598-2-22. The test intervals the system performs come from EN 50172.

Do the same rules apply in every European country?

The technical standards are largely harmonised, but legal requirements are not. Each country decides where emergency lighting is required, which duration applies and how inspections are organised. Always check the national and local rules for your building.