The former German workplace rule ASR A3.4/7 “Safety lighting, optical safety guidance systems” was withdrawn in March 2022. Its updated content now sits in three rules: mainly ASR A2.3 “Escape routes and emergency exits” (section 9, safety lighting), plus ASR A3.4 “Lighting and visual contact” and ASR A1.3 “Safety and health signs”. These are German requirements. Employers need safety lighting where employees would be at risk or could not leave the workplace safely if the normal lighting failed; this is determined in the risk assessment. The lighting design follows EN 1838, for example 1 lx on the centre line of escape routes and 15 lx at high-risk task areas.
Which ASR cover safety lighting today?
The Technical Rules for Workplaces (ASR) put the German Workplaces Ordinance (ArbStättV) into practice. Employers who follow an ASR can assume they meet the ordinance; anyone deviating must demonstrate at least equivalent safety.
Since the rules on escape and traffic routes were reorganised in March 2022, there is no separate ASR for safety lighting any more:
- ASR A2.3 “Escape routes and emergency exits” (March 2022, last amended November 2024): section 9 contains the requirements for safety lighting; it also covers optical safety guidance systems. The 2024 amendment specified dynamic guidance systems and limited the transitional rule for existing safety lighting to buildings erected, or applied for, by 30 April 2025.
- ASR A3.4 “Lighting and visual contact”: general workplace lighting; it took over parts of the former rule.
- ASR A1.3 “Safety and health signs”: exit signs and other safety signage.
Two terms matter for emergency lighting:
- Safety lighting: light that allows people to leave the workplace safely and to stop dangerous work safely when the normal lighting fails.
- Optical safety guidance systems: guidance markings, usually close to the floor, that keep the escape route visible in smoke or darkness. They can be electrically powered or long-afterglow photoluminescent.
Safety lighting and optical guidance systems are different tasks: a ceiling-mounted safety luminaire does not replace a low-level guidance system where the fire safety concept or risk assessment requires one.
Source: BAuA (German Federal Institute for Occupational Safety and Health), ASR A3.4/7 (withdrawn) and ASR A2.3, checked 25 Nov 2026.
Is ASR A3.4/7 still valid?
No. ASR A3.4/7 “Safety lighting, optical safety guidance systems” (May 2009, last amended 2017) was withdrawn in March 2022. Older documents sometimes cite it wrongly as “ASR A3.4/3”. Many fire safety concepts, risk assessments and logbooks still refer to it. Today safety lighting is mainly governed by ASR A2.3. Whether its transitional rule applies to an existing system depends on when the building was erected or applied for – check this in the risk assessment.
When does a workplace need safety lighting?
The ASR does not list specific building types. The deciding factor is the employer's risk assessment. Safety lighting is required where employees could not leave safely or would be exposed to accident risks if the normal lighting failed. Typical reasons:
- many people or people unfamiliar with the building, for example in sales areas,
- large or complex areas such as halls, warehouses and production areas,
- long or winding escape routes, routes through rooms without daylight or in basements,
- night work or work in windowless rooms,
- high-risk task areas, for example at running machinery, in laboratories or near hot baths.
Building regulations may also require safety lighting, for instance in places of assembly, retail premises or high-rise buildings. See emergency lighting requirements.
Which values apply?
The lighting design follows EN 1838. Typical values (check scope and reference areas against the current edition of the standard):
| Area | Minimum value | Response time |
|---|---|---|
| Escape routes (up to 2 m wide) | 1 lx on the centre line | 50 % after 5 s, 100 % after 60 s |
| High-risk task areas | 10 % of normal lighting, at least 15 lx | 100 % within 0.5 s |
| Exit signs | clearly visible, viewing distance matched to size | as for escape routes |
The duration must at least allow all employees to leave safely; at high-risk task areas, the lighting must last as long as the hazard exists. EN 1838 sets at least 1 hour for escape routes; the building permit and fire safety concept may require more. Details: illuminance and duration.
What do employers have to do?
- Risk assessment: determine and document whether and where safety lighting is needed, and update it when the building, use or occupancy changes.
- Design to EN 1838: light escape routes, exits, fire safety equipment and high-risk task areas sufficiently. See planning emergency lighting.
- Signs to ASR A1.3: mark exits and escape routes with ISO 7010 signs.
- Test and maintain: in practice to EN 50172, with monthly function tests, an annual full-duration test and an illuminance measurement every 5 years. See testing intervals.
- Document: record tests and defects in the logbook.
Tip: During inspections by the accident insurance institution or labour inspectorate, it is rarely the luminaire itself that is criticised but missing documentation. A complete logbook is the simplest proof that the employer meets their duties.
With the maintenance contract, NOTLUX carries out the tests and documents them digitally in the app, including the luminaire list and defect tracking.
This article is not legal advice. The risk assessment, building permit and fire safety concept of your workplace are decisive.
Frequently asked questions
Are the ASR legally binding?
The ASR is not a law, but it puts the Workplaces Ordinance into practice. Following it generally means meeting the legal duties; deviations require equivalent safety, justified in the risk assessment.
What became of ASR A3.4/7 (often cited as ASR A3.4/3)?
ASR A3.4/7 was the separate rule for safety lighting and optical safety guidance systems. It was withdrawn in March 2022; its updated content now sits in ASR A2.3 (mainly section 9, safety lighting), ASR A3.4 and ASR A1.3.
Does every office need safety lighting?
No. The risk assessment decides. Small offices with daylight and short, clear escape routes often do not need it; large, windowless or complex areas usually do.
Can photoluminescent signs replace safety lighting?
They can complement safety lighting but not replace it everywhere. Where the risk assessment or building law requires safety lighting, it is needed. See photoluminescent vs illuminated exit signs.