Duties & law

DIN VDE 0108: Is the Old German Standard Still Valid?

6 min readLast updated: October 2026NOTLUX editorial team · TRiALED GmbH
In short

DIN VDE 0108, the former German standard for power installations and safety power supply in buildings for public assembly, has been withdrawn and no longer applies to new installations. Its content is now spread across several standards: EN 1838 (lighting requirements), EN 50172:2024, published in Germany as DIN EN 50172 (VDE 0108-100):2024-10 (design, operation and testing of emergency lighting), EN 50171 (central power supply), DIN VDE 0100-560 (circuits for safety services) and DIN VDE 0100-718 (installations in public buildings and workplaces). The number lives on in the classification “VDE 0108-100”. Systems built to DIN VDE 0108 can usually remain in service, but must be tested and maintained to current rules.

What did DIN VDE 0108 cover?

For decades, DIN VDE 0108 was the central German standard for emergency lighting. It consisted of a general part 1 and further parts for specific building types such as places of assembly, retail buildings, high-rise buildings, restaurants and schools.

A single document covered topics that are now handled by several standards: where safety lighting is needed, required illuminance and duration, how the safety power supply is built (central battery, group battery, self-contained, generator), how the electrical installation is designed and which tests the operator must carry out.

Which standards replaced DIN VDE 0108?

Formerly in DIN VDE 0108Now covered by
Lighting requirements (illuminance, uniformity, response times)EN 1838
Design, installation, operation, testing and documentationEN 50172:2024 (DIN EN 50172 / VDE 0108-100)
Central power supply systemsEN 50171
Circuits and equipment for safety servicesDIN VDE 0100-560 (IEC 60364-5-56)
Installations in buildings for public assemblyDIN VDE 0100-718
Emergency luminaires as productsEN 60598-2-22

Whether a building needs safety lighting at all is no longer set by a VDE standard but by building and workplace law: state building regulations, the building permit, the fire safety concept and the workplace rules ASR A2.3 and ASR A3.4. See the overview of emergency lighting standards.

What does “VDE 0108-100” mean?

The number 0108 has not disappeared entirely. In Germany, EN 50172 carries the VDE classification VDE 0108-100. When you see “VDE 0108” in a tender or test report, check which document is meant:

  • DIN VDE 0108 (parts 1 to 8): the old, withdrawn standard.
  • DIN EN 50172 (VDE 0108-100):2024-10: the current system standard for emergency lighting.
  • DIN VDE V 0108-100-1:2018-12: a national pre-standard used alongside EN 50172. It has been replaced by the 2024 edition and may only be applied until 27 May 2027.

What changed with the 2024 edition is explained in EN 50172:2024.

Can a system built to DIN VDE 0108 stay in service?

Usually yes. Standards do not apply retroactively: a system designed and accepted under the rules in force at the time enjoys grandfathering, unless the building permit or an authority requires otherwise.

Grandfathering covers the installation, not its operation. The system must still be tested regularly (today usually to EN 50172, see testing intervals), defects must be fixed without delay, and the system must still achieve its rated duration. Major alterations, extensions or changes of use often end grandfathering for the affected part.

Tip: Systems built to DIN VDE 0108 are usually 20 years old or more, and spare parts for old central batteries are often hard to find. When major repairs are due, compare them with an upgrade. See upgrading emergency lighting.

What if documents still refer to DIN VDE 0108?

Older building permits, fire safety concepts and logbooks often still cite DIN VDE 0108. That simply reflects the state at installation. Agree with your electrician which standard and intervals apply today and record them in the logbook. Specific requirements in the permit, such as a 3-hour duration, continue to apply. For new luminaires or extensions, specify EN 1838 and EN 50172:2024 rather than DIN VDE 0108.

This article is not legal advice. The requirements for your system follow from the building permit, the fire safety concept and the agreed testing basis.

Frequently asked questions

Is DIN VDE 0108 still valid?

No. DIN VDE 0108 has been withdrawn and is no longer used for new installations. Its content is now mainly found in EN 1838, EN 50172 (VDE 0108-100), EN 50171, DIN VDE 0100-560 and DIN VDE 0100-718.

What is the difference between VDE 0108 and VDE 0108-100?

DIN VDE 0108 is the old, withdrawn standard. VDE 0108-100 is the German VDE classification of the current EN 50172, the system standard for emergency lighting.

Do I have to replace a system built to DIN VDE 0108?

Not automatically. As long as it works, is tested regularly and no major changes are planned, it can usually remain in service. Replacement typically makes sense when spare parts run out, tests keep failing or the building is refurbished.

Which standard replaced DIN VDE 0108 for the safety power supply?

Circuits and equipment for safety services are now covered by DIN VDE 0100-560, central battery systems by EN 50171 and buildings for public assembly by DIN VDE 0100-718.

NOTLUX Symbol
NOTLUX editorial team · TRiALED GmbHSpecialist editors for emergency and safety lighting
NOTLUX

Emergency lighting without worries.

Luminaires, installation and maintenance from a single source – every inspection documented digitally in our app. We start with a free on-site survey and standard-compliant design.

Get a quotein 30 seconds