DIN VDE 0100-560 is the German edition of IEC 60364-5-56, the installation standard for electrical equipment for safety services – everything that must keep working during a power failure: safety lighting, fire alarm and voice alarm systems, smoke extraction or firefighting lifts. It covers safety power sources, the separation of safety circuits from other circuits, their protection and labelling. For emergency lighting, it complements EN 50172 and EN 50171; in Germany, the fire resistance of cables is governed by the cable installation guideline (MLAR). For self-contained emergency luminaires, the requirements are much simpler because each luminaire has its own power source.
What does DIN VDE 0100-560 cover?
The DIN VDE 0100 series covers low-voltage installations. Part 560 is the German version of IEC 60364-5-56 and deals with equipment for safety services: installations that protect people and must therefore work when the normal supply fails, such as safety lighting, fire and voice alarm systems, smoke and heat extraction, firefighting lifts and fire pumps.
The standard does not decide whether a building needs such equipment. That follows from building law, the building permit, the fire safety concept and workplace rules. DIN VDE 0100-560 describes how the electrical installation for it must be built.
Which safety power sources are there?
| Power source | Description | Product standard |
|---|---|---|
| Self-contained battery | battery inside each luminaire | EN 60598-2-22 |
| Central battery (CPS) | shared battery for many luminaires, in its own room | EN 50171 |
| Group battery (LPS) | smaller, power-limited central battery | EN 50171 |
Generators are also safety power sources, but because of their changeover time they are usually combined with batteries for safety lighting. See self-contained vs central battery.
What applies to safety circuits?
The core idea: a fault elsewhere must not disable the safety equipment.
- Separate circuits: safety circuits are independent of other circuits; a short circuit or fire in a normal circuit must not affect them.
- Selective protection: protective devices are coordinated so that a fault only disconnects the affected circuit, not the entire safety supply.
- Protected location: safety power sources and distribution boards are housed so that they keep working as long as possible in a fire, for example in a dedicated battery room.
- Labelling and documentation: safety distribution boards, protective devices and cables are clearly marked and documented.
Where does the MLAR come in?
DIN VDE 0100-560 requires safety cables to keep working long enough in a fire. In Germany, the MLAR (model cable installation guideline, adopted by the federal states) sets out how. For safety lighting it often requires circuit integrity, typically with cables or cable systems rated E30. This mainly affects systems with a central power supply, whose cables run through several fire compartments. See central battery system.
What applies to self-contained luminaires?
With self-contained luminaires, the power source sits inside the luminaire. Many requirements for safety circuits, battery rooms and circuit integrity therefore do not apply: if the supply fails, the luminaire simply switches to its own battery.
The connection matters, though. Self-contained luminaires are normally connected to the final circuit of the normal lighting in the area they serve, so they switch on exactly when the normal lighting there fails.
Tip: Replacing an old central battery system with self-contained luminaires often removes the need for a battery room, fire-resistant cabling and central battery testing. Whether this is possible depends on the fire safety concept. See replacing central battery systems.
NOTLUX Series 19 luminaires are self-contained luminaires with self-test that can be tested and documented via the app.
This article does not replace professional design. Safety circuits must be installed and modified by a qualified electrician.
Frequently asked questions
Who does DIN VDE 0100-560 apply to?
To electrical contractors and designers who install or modify equipment for safety services. Operators are affected indirectly: they must ensure their system is properly installed and tested.
What is the difference between DIN VDE 0100-560 and EN 50172?
DIN VDE 0100-560 covers the electrical installation of all equipment for safety services. EN 50172 is the specific system standard for emergency lighting, covering design, operation, testing and documentation.
Do self-contained luminaires need fire-resistant cables?
Usually not. Each luminaire has its own power source and keeps working if its supply fails. Circuit integrity under the MLAR mainly concerns cables from central battery systems to the luminaires.
Did DIN VDE 0100-560 replace the old DIN VDE 0108?
Partly. The safety power supply requirements of the former DIN VDE 0108 are now mainly in DIN VDE 0100-560 and EN 50171; the emergency lighting requirements themselves are in EN 1838 and EN 50172.